Model | Wygląd | Cena falownika - kup-online | Napięcie wejściowe | Moc | Napięcie wyjściowe (VDC) | Prąd wyjściowy |
S8JX-G01505CD | - | 100 to 240 VAC (free) (80 to 370 VDC *) S8JX-G15005[][]: Switchable between 100 to 120 VAC and 200 to 240 VAC. (DC power cannot be input.) |
15 W | 5 V | 3 A | |
S8JX-G01512CD | kup teraz | 15 W | 12 V | 1.3 A | ||
S8JX-G01515CD | - | 15 W | 15 V | 1 A | ||
S8JX-G01524CD | kup teraz | 15 W | 24 V | 0.65 A | ||
S8JX-G01548CD | - | 15 W | 48 V | 0.35 A | ||
S8JX-G03505CD | - | 35 W | 5 V | 7 A | ||
S8JX-G03512CD | kup teraz | 35 W | 12 V | 3 A | ||
S8JX-G03515CD | - | 35 W | 15 V | 2.4 A | ||
S8JX-G03524CD | kup teraz | 35 W | 24 V | 1.5 A | ||
S8JX-G03548CD | - | 35 W | 48 V | 0.75 A | ||
S8JX-G05005CD | - | 50 W | 5 V | 10 A | ||
S8JX-G05012CD | kup teraz | 50 W | 12 V | 4.2 A | ||
S8JX-G05024CD | kup teraz | 50 W | 24 V | 2.1 A | ||
S8JX-G05048CD | - | 50 W | 48 V | 1.1 A | ||
S8JX-G10005CD | - | 100 W | 5 V | 20 A | ||
S8JX-G10012CD | kup teraz | 100 W | 12 V | 8.5 A | ||
S8JX-G10024CD | kup teraz | 100 W | 24 V | 4.5 A | ||
S8JX-G10048CD | - | 100 W | 48 V | 2.1 A | ||
S8JX-G15005CD | - | 150 W | 5 V | 30 A | ||
S8JX-G15012CD | kup teraz | 150 W | 12 V | 13 A | ||
S8JX-G15024CD | kup teraz | 150 W | 24 V | 6.5 A | ||
S8JX-G15048CD | - | 150 W | 48 V | 3.3 A | ||
S8JX-G30005CD | - | 100 to 120 VAC 200 to 240 VAC (Switchable) |
300 W | 5 V | 60 A | |
S8JX-G30012CD | kup teraz | 300 W | 12 V | 27 A | ||
S8JX-G30024CD | kup teraz | 300 W | 24 V | 14A | ||
S8JX-G30048CD | - | 300 W | 48 V | 7A |
* The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).
Montaż na ścianie za pomocą uchwytów
Model | Wygląd | Cena | Napięcie wejściowe | Moc | Napięcie wyjściowe (VDC) | Prąd wyjściowy |
S8JX-G60005C | - | 100 to 120 VAC 200 to 240 VAC (Switchable) |
600 W | 5 V | 120A | |
S8JX-G60012C | kup teraz | 600 W | 12 V | 53A | ||
S8JX-G60024C | kup teraz | 600 W | 24 V | 27A | ||
S8JX-G60048C | - | 600W | 48 V | 13A |
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 15 W | 35 W | ||
Efficiency | 68% min. | 73% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | ||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 0.4 A max. | 1 A max. | |
200 V input | 0.25 A max. | 0.6 A max. | ||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | ||
200 V input | 40 A max. | |||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | ||
Ripple *3 | 2% (p-p) max. | |||
Input variation influence | 0.4% max. with AC input voltage | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | |||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 | 105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | No | |||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
No | |||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI | Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | |||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | |||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 250 g max. |
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 50 W | 100 W | ||
Efficiency | 5 V Models | 76% min. | 76% min. | |
12 V Models | 81% min. | 81% min. | ||
24 V Models | 83% min. | 83% min. | ||
48 V Models | 82% min. | 83% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | ||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 1.4 A max. | 2.5 A max. | |
200 V input | 0.8 A max. | 1.5 A max. | ||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | ||
200 V input | 40 A max. | |||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | ||
Ripple *3 | 2% (p-p) max. | |||
Input variation influence | 0.4% max. with AC input voltage | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | |||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 | 105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | No | |||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
No | |||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI | Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | |||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | |||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 300 g max. | 550 g max. |
Input specification | 100/200 V switchable | 100 to 240 V input | |||
---|---|---|---|---|---|
Power ratings *1 | 150 W at 5 V | 150 W at 12 V | 150 W at 24 or 48 V |
||
Efficiency | 5 V Models | 78% min. | --- | --- | |
12 V Models | --- | 79% min. | --- | ||
24 V Models | --- | --- | 86% min. | ||
48 V Models | --- | --- | 85% min. | ||
Input | Voltage *2 | Switchable between 100 to 120 VAC (allowable range: 85 to 132 VAC) and 200 to 240 VAC (allowable range: 170 to 264 VAC). |
100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) |
||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | ||||
Current *3 |
100 V input | 3.5 A max. | 3.6 A max. | 3.5 A max. | |
200 V input | 2.1 A max. | 2.2 A max. | 2.1 A max. | ||
Harmonic current emissions | --- | ||||
Leakage current *3 |
100 V input | 0.5 mA max. | |||
200 V input | 1 mA max. | ||||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | |||
200 V input | 40 A max. | ||||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | |||
Ripple *3 | 2% (p-p) max. | ||||
Input variation influence | 0.4% max. (with AC input voltage) | ||||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | ||||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | ||||
Hold time *3 | 20 ms min. | ||||
Addi- tional func- tions |
Overload protection *6 | 105% to 175% of rated load current, voltage drop, automatic reset |
105% to 175% of rated load current, voltage drop, intermittent, automatic reset |
||
Overvoltage protection *7 | Yes | ||||
Overheat protection | No | ||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | ||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Protective circuit operation indicator |
No | ||||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
|||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | ||||
Output indicator | Yes (Color: Green) | ||||
EMI | Conducted Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | ||||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | |||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | ||||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
|||||
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
|||||
SEMI | --- | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 800 g max. | 700 g max. | 600 g max. |
Input specification | 100/200 V (Selected) | |||
---|---|---|---|---|
Power ratings *1 | 300 W | 600 W | ||
Efficiency | 5 V models | 71% min. | 72% min. | |
12 V models | 75% min. | 78% min. | ||
24 V models | 82% min. | 80% min. | ||
48 V models | 82% min. | 80% min. | ||
Input | Voltage *2 | 100 to 120 VAC (allowable range: 85 to 132 VAC) 200 to 240 VAC (allowable range: 170 to 264 VAC) (Switchable) |
||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current *3 |
100 V input | 8 A max. | 16 A max. (5V, 12V, 48V) 14 A max. (24V) |
|
200 V input | 4.5 A max. | 9 A max. (5V, 12V, 48V) 8 A max. (24V) |
||
Harmonic current emissions | --- | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 25 A max. | 30 A max. | |
200 V input | 50 A max. | 60 A max. | ||
Output *4 |
Voltage adjustment range *5 | -10% to 15% (with V. ADJ) (48-V models: ±10%) | ||
Ripple *3 | 2.8% (p-p) max.(5V) *6 2% (p-p) max.(12V, 24V, 48V) |
3.8% (p-p) max.(5V) *6 2% (p-p) max.(12V) *6 2% (p-p) max.(24V, 48V) |
||
Input variation influence | 0.4% max. | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. | |||
Startup time | 650 ms max. | 500 ms max. | ||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *7 | 105% to 175% of rated load current, Inverted L voltage drop, the circuit will be shut OFF when the overload exceeds 5 s. (5V, 12V) *10 voltage drop, intermittent, automatic reset. (24V, 48V) |
105% to 175% of rated load current, Inverted L voltage drop, the circuit will be shut OFF when the overload exceeds 5 s. *10 |
|
Overvoltage protection *8 | Yes (5V, 12V) *10 Yes (24V, 48V) *10 |
Yes *10 | ||
Overheat protection | Yes (5V, 12V) *10 N0 (24V, 48V) *10 |
Yes *10 | ||
Parallel operation | Yes (up to 5 units) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation indicator |
Yes (color: red) (5V, 12V) No (24V, 48V) |
Yes (color: red) | ||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI | Conducted Emissions *3 |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *11 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *11 *12 | |||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *13 | UL UR: UL 508 (Recognition), UL 60950-1 (Recognition) | |||
cUR: CSA C22.2 No. 60950-1 | ||||
EN/VDE: EN50178 (= VDE 0160), Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
Weight *9 | 1,800 g max. (5V, 12V) 1,600 g max. (24V, 48V) |
2,500 g max. |
Input specification | 100 to 240 V input | ||||
---|---|---|---|---|---|
Power ratings *1 | 50 W | 100 W | 150 W | ||
Efficiency | 5 V Models | 73% min. | 78% min. | 79% min. | |
12 V Models | 76% min. | 78% min. | 78% min. | ||
24 V Models | 77% min. | 81% min. | 81% min. | ||
48 V Models | 80% min. | 81% min. | 82% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | |||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | ||||
Current *3 |
100 V input | 0.75 A max. | 1.4 A max. | 2.1 A max. | |
200 V input | 0.4 A max. | 0.75 A max. | 1.1 A max. | ||
Power factor | 0.9 min. | ||||
Harmonic current emissions | Conforms to EN61000-3-2 | ||||
Leakage current *3 |
100 V input | 0.5 mA max. | |||
200 V input | 1 mA max. | ||||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 17.5 A max. | |||
200 V input | 35 A max. | ||||
Output *4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | |||
Ripple *3 | 2% (p-p) max. This shall be 3% (p-p) or less when the ambient temperature is less than 0 °C (for only 5 V type). |
||||
Input variation influence | 0.4% max. with AC input voltage | ||||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | ||||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | ||||
Startup time | 1,000 ms max. | ||||
Hold time *3 | 20 ms min. | ||||
Addi- tional func- tions |
Overload protection *6 | 105% to 160% of rated load current, voltage drop, intermittent, automatic reset |
105% to 160% of rated load current, voltage drop, automatic reset |
||
Overvoltage protection *7 | Yes | ||||
Overheat protection | No | ||||
Parallel operation | No (However, backup operation is possible; external diodes required.) | ||||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | ||||
Alarm indicator | No | ||||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing or condensation). |
|||
Storage temperature | - 25 to 75 °C (with no icing or condensation) | ||||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | ||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
||||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | ||||
Output indicator | Yes (Color: Green) | ||||
EMI | Conducted Emissions |
Conforms to EN 55011 Group 1 Class B and based on FCC Class B *9 | |||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *9 | ||||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | |||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | ||||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | ||||
Surge | Conforms to EN61000-4-5 | ||||
Conducted Disturbance |
Conforms to EN61000-4-6 | ||||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | ||||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | ||||
cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 |
|||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
|||||
SEMI | SEMI F47-0706 (200-VAC input) | ||||
Weight *8 | 370 g max. | 550 g max. | 590 g max. |
Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 300 W | 600 W | ||
Efficiency | 5 V Models | 75% min. | 76% min. | |
12 V Models | 77% min. | 76% min. | ||
24 V Models | 79% min. | 78% min. | ||
48 V Models | 78% min. | 79% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *8) | ||
Frequency *2 | 50/60 Hz (47 to 63 Hz) | |||
Current *3 |
100 V input | 4.5 A max. | 8.7 A max. | |
200 V input | 2.2 A max. | 4.3 A max. | ||
Power factor | 0.9 min. | |||
Harmonic current emissions | Conforms to EN61000-3-2 | |||
Leakage current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush current (for a cold start at 25 °C) *3 |
100 V input | 17.5 A max. | ||
200 V input | 35 A max. | |||
Output *4 |
Voltage adjustment range *5 | -10% to 15% (with V. ADJ) (5 V, 48 V models: ±10%) | ||
Ripple *3 | 2% (p-p) max. 3% (p-p) max. (for only 5 V type) *12 |
|||
Input variation influence | 0.4% max. | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. | |||
Startup time | 1,000 ms max. | |||
Hold time *3 | 20 ms min. | |||
Addi- tional func- tions |
Overload protection *6 | 105% to 160% of rated load current, voltage drop, intermittent, automatic reset. |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | Yes | |||
Parallel operation | Yes (up to 5 Power Supplies) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Remote sensing | Supported | |||
Remote control | Supported | |||
Alarm detection indication | Yes (color: red) | |||
Alarm output | Provided, open-collector output, 30 VDC max, 50 mA max. | |||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog. (with no icing or condensation). |
||
Storage temperature | - 25 to 75 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 100 mA) 100 VAC for 1 min. (between all outputs and RC terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs and ALM terminals; detection current: 20 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC |
|||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions |
|||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions *10 | |||
Output indicator | Yes (Color: Green) | |||
EMI | Conducted Emissions *3 |
Conforms to EN 55011 Group 1 Class B and based on FCC Class B *11 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class B *11 | |||
EMS | Electrostatic Discharge |
Conforms to EN61000-4-2 | ||
Radiated Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *8 | UL UR: UL 508 (Recognition) *13 UL Listed: UL508 (Listing) *14 UL UR: UL 60950-1 (Recognition) |
|||
cUR: CSA C22.2 No.107.1, CSA C22.2 No. 60950-1 | ||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III, EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0706 (200-VAC input) | |||
Weight | 1,200 g max. *9 | 1,800 g max. *9 |